| ISSUE |
POSSIBLE SOLUTION |
| “The sensor is not tracking the shaft position at all! Reading remains
at the ‘offset’ setting!” |
Verify that the parameter ‘scale’ is not set to ‘0.000’. “Scale” must
be equal to the circumference of the pulley. Use ‘aQ1!’ to verify as per
manual or use the LED display. Set the ‘scale’ using ‘aS1+SCALE!’, or use
the display. |
| “The sensor appears to be drifting from the correct level readings!” |
-
Verify that the ‘scale’ is equal to the circumference of the pulley being
used, typically 0.375m. This can be verified with the ‘aQ1!’ command. We
have seen people accidentally change the ‘scale’ to some other value which
will cause erroneous readings. Set the ‘Scale’ with the ‘aS1+SCALE!’ command.
See the manual.
-
Check that the 9V battery backup is at least 7V, if not replace it. During
power interruptions the 9V battery maintains continuous shaft position
tracking. If this battery is low the sensor may be resetting itself to
the ‘offset’ every time there is a power glitch.
Verify that the algebraic sign of the “scale” corresponds to the configuration
of your installation. REMEMBER, use ‘+’ if clockwise rotation corresponds
to rising water levels. Otherwise use ‘-‘.
|
| “Cannot communicate with the sensor!” |
-
Verify the sensor address. You can do this using ‘?I!’ if there are no
other SDI-12 sensors on the bus. This can also be done via the LED display
(with ‘/D’ option).
-
Check connections (white = SDI-12 data, red = +12VDC, black = ground).
|